ไฮไลท์
KEW 2062 Clamp Power Meter
A tear drop shape jaw with the conductor size 55 mm: Convenient to use at a small-sized office and factory
・Current up to 1000A rms
・Voltage up to 1000V rms
・Harmonics up to 30th
・Various measurement functions: current, voltage, power, harmonics
and phase detection
・LCD can display simultaneously the values of voltage and frequency
or power and power factor
・Each degree of harmonics can be shown on the LCD of the tester
ข้อมูล
น้ำหนัก
บาร์โค้ด
ลงสินค้า
อัพเดทล่าสุด
รายละเอียดสินค้า
Wiring connections 1P2W, 1P3W, 3P3W, 3P4W
Measurements and 
parameters
Voltage, Current, Frequency, Active power, Reactive power, 
Apparent power, Power factor(cosθ), Phase angle, 
Harmonics(THD-R/THD-F), Phase rotation
ACV
 
Range 1000V
Accuracy ±0.7%rdg±3dgt (40.0 - 70.0Hz)
±3.0%rdg±5dgt (70.1 - 1kHz)
Crest factor 1.7 or less
ACA
 
Range 40.00/400.0/1000A (3 range auto)
Accuracy ±1.0%rdg±3dgt (40.0 - 70.0Hz)
±2.0%rdg±5dgt (70.1 - 1kHz)
Crest factor 3 or less on 40.00A/400.0A range, 
3 or less 1500A peak on 1000A range
Frequency
 
Display Range 40.0 - 999.9Hz
Accuracy ±0.3%rdg±3dgt
Active power
 
Range 40.00/400.0/1000kW
Accuracy ±1.7%rdg±5dgt (PF1, sine wave, 45 - 65Hz) 
Apparent power
 
Range 40.00/400.0/1000kVA
Accuracy ±1dgt against each calculated value 
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Reactive power
 
Range 40.00/400.0/1000kVar
Accuracy ±1dgt against each calculated value 
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Power factor
 
Display Range -1.000 - 0.000 - +1.000
Accuracy ±1dgt against each calculated value 
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Phase angle (1P2W only)
 
Display Range -180.0 - 0.0 - +179.9
Accuracy ±3.0°
Harmonics RMS(Content rate)
 
Analysis order 1st - 30th order
Accuracy ±5.0%rdg ± 10dgt (1 - 10th)
±10%rdg ± 10dgt (11 - 20th)
±20%rdg ± 10dgt (21 - 30th)
Total harmonics THD-R/THD-F 
 
Display Range 0.0% - 100.0%
Accuracy ±1dgt against the calculated results of each measured value
Phase rotation ACV 80 - 1100V (45 - 65Hz)
Other functions MAX/MIN/AVG/PEAK, Data hold, Back light, Auto power off
General
 
Power source LR6(AAA)(1.5V) ×2
Continuous 
measuring time
Approx. 58 hours
Conductor size φ55mm max.
Dimensions / Weight 247(L) × 105(W) × 49(D) mm / Approx.490g(including batteries)
Applicable Standards IEC 61010-1, IEC 61010-2-032, IEC 61326-1,-2-2 (EMC), IEC 60529 (IP40)
CAT IV 300V / CAT lll 600V / CAT ll 1000V Pollution degree 2

Accessories 7290 (Voltage test lead set)
9198 (Carrying case)
LR6(AAA)×2, Instruction Manual
เงื่อนไขอื่นๆ
Tags

วิธีการชำระเงิน

สั่งซื้อสินค้าเรียบร้อยแล้ว รบกวนรอทางร้านติดต่อกลับ หรือแอดไลน์ LINE @onebanmor